Displaying report 1-1 of 1.
Reports until 16:51, Wednesday 12 June 2019
H1 CAL (CDS)
jeffrey.kissel@LIGO.ORG - posted 16:51, Wednesday 12 June 2019 (49866)
Channels Not Monitored and Not touched by Guardian -- SDF list Clean up for CAL
J. Kissel

Dave have recently found that there are a small collection of EPICs settings that are both NOT touched by Guardian and NOT monitored in the SDF system (see O3SDFReview in the CDS wiki). Today, during the commissioning period, I reviewed and either monitored or justified why to leave them unmonitored for those channels in the CAL models. In summary -- very little change, some channels that should be monitored are now monitored, and others are known that they should be not monitored.


CAL INJ
    Now monitored
        H1:FEC-42_BURT_RESTORE     (button to demand a burt restore of safe.snap during start up. shouldn't be changing, and isn't even available to change on GDSTP screen. Should be monitored)
        H1:FEC-42_DACDT_ENABLE     (button to switch on the DAC doutone readback in to the 31st channel of the ADC )

    Leaving unmonitored
        H1:CAL-INJ_TINJ_$(ENDED/PAUSE/START/STATE/TYPE)      (actually readbacks written to by TINJ guardian node about injection information. should remain unmonitored.)
        H1:CAL-INJ_TRANSIENT_$(GAIN/TRAMP)                   (used to turn OFF hardware injections, which happens during a GRB alert, and potentially during observe)
        H1:CAL-INJ_TINJ_ENABLE                               (used to turn OFF hardware injections, which happens during a GRB alert, and potentially during observe)

CAL CS
    Now Monitored 
        H1:CAL-CS_TDEP_SUS_$(L1,L2,L3)_LINE_END_SW           (toggle switch that determines which ETM is being used to inject calibration lines. Should not be changing and should be monitored.)
Displaying report 1-1 of 1.