J. Kissel Dave have recently found that there are a small collection of EPICs settings that are both NOT touched by Guardian and NOT monitored in the SDF system (see O3SDFReview in the CDS wiki). Today, during the commissioning period, I reviewed and either monitored or justified why to leave them unmonitored for those channels in the CAL models. In summary -- very little change, some channels that should be monitored are now monitored, and others are known that they should be not monitored. CAL INJ Now monitored H1:FEC-42_BURT_RESTORE (button to demand a burt restore of safe.snap during start up. shouldn't be changing, and isn't even available to change on GDSTP screen. Should be monitored) H1:FEC-42_DACDT_ENABLE (button to switch on the DAC doutone readback in to the 31st channel of the ADC ) Leaving unmonitored H1:CAL-INJ_TINJ_$(ENDED/PAUSE/START/STATE/TYPE) (actually readbacks written to by TINJ guardian node about injection information. should remain unmonitored.) H1:CAL-INJ_TRANSIENT_$(GAIN/TRAMP) (used to turn OFF hardware injections, which happens during a GRB alert, and potentially during observe) H1:CAL-INJ_TINJ_ENABLE (used to turn OFF hardware injections, which happens during a GRB alert, and potentially during observe) CAL CS Now Monitored H1:CAL-CS_TDEP_SUS_$(L1,L2,L3)_LINE_END_SW (toggle switch that determines which ETM is being used to inject calibration lines. Should not be changing and should be monitored.)