Displaying report 1-1 of 1.
Reports until 10:25, Tuesday 18 June 2019
H1 PSL
jason.oberling@LIGO.ORG - posted 10:25, Tuesday 18 June 2019 (50028)
PSl Power Watchdog Reset (FAMIS 10715)

I reset both PSL power watchdogs at 17:19 UTC (10:19 PDT).  This closes FAMIS 10715.

Also, while resetting the watchdogs I noticed the Inner Loop ISS diffracted % was down around 1%.  This should be between 2%-3%, so I adjusted the ISS RefSignal from -2.07 V to -2.05 V; this brought the diffracted % to ~2.0%.  This change was accepted in SDF.

Displaying report 1-1 of 1.