david.barker@LIGO.ORG - posted 22:56, Tuesday 23 July 2019 - last comment - 00:49, Wednesday 24 July 2019(50758)
Electrical storm power glitch crashed all Dolphin'ed front end computers
Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 22:59, Tuesday 23 July 2019 (50759)

opened FRS13311

david.barker@LIGO.ORG - 23:05, Tuesday 23 July 2019 (50760)

All front end can see their respective IO Chassis, I'm starting the model recovery.

david.barker@LIGO.ORG - 23:48, Tuesday 23 July 2019 (50762)

All models restarted. Jonathan reports DAQ is in good health.

Long range dolphin is down, I'm investigating.

david.barker@LIGO.ORG - 00:07, Wednesday 24 July 2019 (50763)

h1cdsrfm computer had restarted itself (it is a diskless front end, but the only one which got rebooted). I had to remember how to start the code since we haven't done so since Nov 2018.

Code is running, bad news is that we are not receiving anything from EY. This could be a possible problem with the EY remote Adnaco chassis. No, I can see all three Dolphin IX cards.

Images attached to this comment
david.barker@LIGO.ORG - 00:49, Wednesday 24 July 2019 (50765)

I've tried several reboots of h1cdsrfm, but I still get the problem that IPC from EY to the corner station is failing (CS to EY is working). 