jeffrey.bartlett@LIGO.ORG - posted 13:32, Tuesday 06 August 2019 (51076)
Bi-Monthly HEPI Fluid Level Checks (FAMIS 13483)
   End-Y - HEPI fluid level is 9 0/16 unchanged from last check. No new leaks observed. Changed out some of the absorbent pads that had become saturated. 

   End-X - HEPI fluid level is 8 8/16, unchanged from last check. No new leaks observed. 

   Corner Station - HEPI fluid level is 8 6/16, down by -1/16 from last check. 
   The leak between the pump housing and the motor's output shaft may be growing a little. Cleaned up the area and changed out the absorbent pad. Will put down a drip pan to get an idea of drip amount. There is another small leak at the other end of the pump station near the pressure gauge for the accumulator rail. wiped up and placed a clean absorbent pad.        