david.barker@LIGO.ORG - posted 14:27, Saturday 10 August 2019 - last comment - 14:36, Saturday 10 August 2019(51193)
EY chiller yard alarm, supply water temperature over 50F

Another EY chilled water overtemp, attached 24 hour trend. Bubba is investigating.

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 14:36, Saturday 10 August 2019 (51194)

Reminder to the group: this alarm is triggered if the EY chiller supply water temperature exceeds 49F for 5 minutes or more. The above trend suggests the temperature went above 50F yesterday afternoon, but not for more than 5 minutes.

 