Corey, Dave:
Corey power cycled h1susey, h1seiey and h1iscey. This cleared the DAQ errors with EX and corner station ISC. h1susey is running, both SEI and ISC IOP models have a negative IRIG-B excursion which should clear soon. In the mean time their DAQ and IPC status is bad.
Remaining IPC errors are because h1cdsrfm is not responsive. I've taken this out of Dolphin and am remotely reseting it.
After the trip to EY, Dave said I could bring back all the tripped SUS & SEI at EY. Started with ETMy & TMS. Then moved on to HEPI, and then SEI ETMy.
Did notice HPI_ETMY_SC a message for this node (via SEI_CONF) which said "Configuration is not correct, re-request to recover"....there was also some a YELLOW indicator for this node. After re-requesting CONFIG_SC_ON, this Node was good.
This made everything for EY GREEN.
Noticed YELLOW for the B3_SEI & B1_SEISEI guardian nodes. Which showed SEI_ITMx (&y) had notifications for their ISI ITM ST2 guardian nodes for both x & y say "SETPOINT CHANGES. see SPM DIFFS for differences". Not sure what to do about those SPM Diffs. But other than that, all EY SEI guardian nodes are green.