Displaying report 1-1 of 1.
Reports until 18:03, Tuesday 22 October 2019
H1 CDS (CDS, SEI)
patrick.thomas@LIGO.ORG - posted 18:03, Tuesday 22 October 2019 - last comment - 08:50, Thursday 24 October 2019(52629)
BRS computer updates for heater install
Oct. 18 - 22 2019

h1brsex:

After I ran svn update on C:\SlowControls the applications in trunk/EPICS/Utilities/Bin gave the error in the attached screenshot. I have reverted the working copy of this directory to revision 4189 to get the EPICS IOC to run.

I scanned for the Beckhoff terminals that Filiberto installed and added them to the IO in the solution.

I added the PLC variables and code for the addition of the heater and linked the variables to the added IO terminals as instructed by Eyal. There was some confusion because the size of the HEATCTRLOUT PLC variable and the EL4134 channel it links to do not match. Only the first 16 bits of the PLC variable are linked.

I removed from svn the files in trunk/TwinCAT3/BRS/H1BRSEX that are automatically generated.

I fixed the paths in brsxEPICS.bat and brsxEPICS.cmd. These were pointing to an old copy of the code that is not in svn. I added lines to brsxEPICS.cmd to generate the ini and req files.

I installed WinSCP and copied the generated ini and req files to /opt/rtcds/userapps/release/ecat/h1brsex.

h1brsey:

I ran svn update. On this computer the applications in trunk/EPICS/Utilities/Bin ran without error.

The additional Beckhoff terminals have not yet been connected at this station so I only added the PLC code.

I removed from svn the files in trunk/TwinCAT3/BRS/H1BRSEY that are automatically generated.

I changed the names of the ini and req files in brsyEPICS.cmd to h1brsey.ini and h1brsey.req.

I installed WinSCP and copied the generated ini and req files to /opt/rtcds/userapps/release/ecat/h1brsey.
Images attached to this report
Comments related to this report
patrick.thomas@LIGO.ORG - 08:50, Thursday 24 October 2019 (52679)
Added terminals and links for h1brsey.
Displaying report 1-1 of 1.