Reports until 07:58, Sunday 03 November 2019
H1 General
jeffrey.bartlett@LIGO.ORG - posted 07:58, Sunday 03 November 2019 (52937)
Low Pressure Alarm on PT-199 Inst Air
   At 15:31 (07:31) received low pressure alarm on PT-199 Instrument Air. Cheryl trended the channel and found the pressure dropping rapidly; passing through 50PSIG. 

   I called Kyle. He gave me instructions on running the compressor by hand. Went to Chiller Yard and turned on both compressors by hand. Both worked in the Hand position but did not run in the Auto position. Switched compressor #1 to Hand and built pressure up to  95PSIG. Put switch back into the Auto position. 

  As of 15:52 (07:52) Kyle was on site looking into the problem.