tyler.guidry@LIGO.ORG - posted 09:25, Monday 11 November 2019 - last comment - 12:26, Monday 11 November 2019(53151)
Instrument Air Isolation 2.0
Tyler G. Chris S.

The instrument air compressor received different equipment isolation to (hopefully) mitigate noise during operation. The changes made were springs which deflected at a lower weight (approx .830" at 250lbs of load) as well as a soft silicone pad placed between the springs housing and the concrete slab. This task was completed at approx 8:45am
Comments related to this report
chandra.romel@LIGO.ORG - 11:48, Monday 11 November 2019 (53156)DetChar, PEM

Tagging DetChar & PEM

vladimir.bossilkov@LIGO.ORG - 12:26, Monday 11 November 2019 (53158)

I have attached the spectrogram of the strain, where you can see the air compressor noise coming through - at first look, it seems it has not gotten better.

8:45 am would make it 16:45 in the attached image (right where the big red bar is).