Step 1 of modification to the CS instrument air supply

Today, I performed the 1st stage of modification to the instrument air supply setup for the Corner Station which, when completed, will reduce the compressor's runtime (duty-cycle) by ~65%.  Step 1 - added double check-valves to the output of the drying towers.  Also, added isolation valves and Tees w/swagelok ports between the reciever tank and the pressure switches (both LEAD and LAG). 

Comments related to this report
chandra.romel@LIGO.ORG - 17:02, Tuesday 03 December 2019 (53665)

This is an improvement in reducing energy and increasing equipment life. Additionally, we plan to replace this reciprocating piston style compressor unit with a scroll style similar to original.