Displaying report 1-1 of 1.
Reports until 14:50, Monday 11 February 2013
H1 PSL
michael.rodruck@LIGO.ORG - posted 14:50, Monday 11 February 2013 (5454)
Frontend power monitor fixed

A month ago when we restarted the laser we noticed the frontend power monitor was reading only 6W. This was tracked down to a gain setting that was modified and not entered into the safe.snap file, so when we rebooted the computer frontends for the 2.6 code upgrade the incorrect gain value was entered. I've changed back to the correct setting and updated the safe.snap file, and we are now reading 31W.