Displaying report 1-1 of 1.
Reports until 16:26, Wednesday 22 January 2020
H1 CDS
david.barker@LIGO.ORG - posted 16:26, Wednesday 22 January 2020 (54659)
We'll clear the latched timing bit on h1iopasc0 on the next lock-loss

The red timing bit on the h1iopasc0 model is a latched signal, it was raised when the IOP momentarily ran long (17uS) at 06:37 PST this morning. Since this error is not repeating, we will wait until the next lock-loss to clear it. In the attachment, the cpu processing time and the model's state-word are trended, showing the 2nd bit of the state word (the timing bit) was raised when the cpu ran out to 17uS during one cycle of the 65536 cycles in that second.

Images attached to this report