Reports until 08:58, Monday 10 February 2020
H1 SEI
hugh.radkins@LIGO.ORG - posted 08:58, Monday 10 February 2020 (55006)
H1 Corner Station HEPI Pump Servo Restart

The CS HEPI Pump Servo program froze ~1258utc today.  Recovery was easy and typical.  Details:

Following the OPS WIKI, https://cdswiki.ligo-wa.caltech.edu/wiki/SEI, wiki text is verbatum in blue and my comments are in red:

HEPI Pump Stations

You are here likely because an Alarm on the HEPI Differential Pressure. Couple things: is the Alarm Invalid or other? Is it Momentary, or Ongoing?

Invalid Alarm This was our situation this morning

If the alarm is Invalid, the Pump Controller medm is likely white boxed; look for this under the Sitemap HEPI pulldowns. A restart of the servo is required. Don't panic though, the system may still actually be running and might be able to be restarted without losing the HEPI Platform's Isolation state. If the HEPI Platforms have not tripped, this is likely the situation. If power to the servo computer wasn't interrupted, the output from the servo to the VFD may be steady and keeping the Pressure near Okay.

Again, exactly the case this morning.  Went to the pump stations and the dial gauge on the pumps were reading ~80psi, normal.  The computer appeared to be running but the heartbeat was flatlined.  I did not restart the computer.

Restarting the White Boxed Servo: If your servo is not running (white boxed medm) restart it with the following sequence:

If the HEPI platforms are still isolating (not tripped,) trend the VOUT channel: H1:HPI-PUMP_L0/EX/EY_CONTROL_VOUT for use in restarting. The conditions would indicate the servo computer has latched its output to the VFD and the Pump Motors are running 'open loop' but with the servo dead, you don't know the drive level. The trend will tell you what it was when it stopped, and when. Now

The trends showed that the last output from the PID to the VFD was ~1085

continue with the following sequence to restart the servo:

1. ssh controls@h1hpipumpctrll0 For the Corner Station

2. cd target-new For the Corner Station

3. sudo ./run

Logging in was trivial but the medm took a good while to come completely alive but it did.  During this period, the IFO dropped out of observing as two fields changed: 1) the PID Setpoint level, I could hardcode that into the dB, and 2) the Servo Control Auto/Manual button.  This must come up in manual mode so the program does not write anything to the VFD.  This is what allows the HEPI system to keep running in this situation. If it were in Auto, the PID would push a zero before it had a chance to calculate and process a reasonable value.  Maybe a smart dB programmer could work this out but for now, this is what we (I) do.

This should restart the servo and the medm should come alive. Do not push any buttons, you don't want the servo to process any records. Note the pressures, these are valid and hopefully not too far from nominal. However, the servo will not have processed any records yet and the 0 counts output to the VFD is not valid. The servo starts in a safe state, most importantly Manual Control and no Burt Restore is requied. Now using the VOUT value from the trends before the drop out, put this value into EPICS:

caput H1:HPI-PUMP_L0/EY/EX_CONTROL_VOUT value. caput the 1085 gleaned from the trends above.

Okay, that's it.  Sure, look at the 6 hour trend plot attached.