Gerardo, Richard, Dave:
Gerardo power cycled the h1pemmx front end system while he was onsite this morning. The sequence was cpu off, io-chassis off, io-chassis on, cpu on. I restarted h1ioppemmx about a dozen times but always got a DAQ timing error. I then remembered we had seen this before, and it was resolved by a soft reboot after the power cycle. After soft booting h1pemmx the iop model started correctly on the second try. (the mid stations front ends do not have an IRIGB signal and get their time remotely with typically a 50% success rate).
h1pemmx is running again, attached is a 7 day minute-trend plot of the vault magnetometers