HAM-ISI & HAM-HEPI model updates

The SEI electronics wiring diagrams were recently updated.

Models were modified to reflect those changes on our Units:
HAM2-ISI
HAM3-ISI
HAM1-HEPI
HAM2-HEPI
HAM3-HEPI

Models were recompiled and wiring was checked. IPS readouts match values recorded prior to re-wiring. Turning sensor's interface chassis on/off is reflected on the correct channels. Actuation was checked on HAM3-ISI, confirming the DAC number for HAM2-ISI (only 2 DACs on HAM23 IO chassis).

Damping loops, and level 2 Isolation loops were closed, on HAM3-ISI. We used the latest blend filters created during the IMC test. Controls were not tested after the vent. The current stability of these controllers confirms both the new wiring/models and the robustness of the control loops, in Air.

Hence, these control loops will be used to help IO locking the mode cleaner during the upcoming weeks.

Comments related to this report
hugo.paris@LIGO.ORG - 11:23, Thursday 28 February 2013 (5607)

Updated models were commited in the SVN