WP3758. All three PEM systems were restarted with new code today (h1peml0,mx,ey). After the filter modules were removed some weeks ago, the RCG generated MEDM screens for ADC became white-screened. Today's change installed EPICS OUTPUTparts in place of the missing filter modules to fix the MEDM screens (see attachments). I noticed that I had two difference BLRMS parts, one with a fllter in the input arm (h1pemmx and h1pemey) and one without the filter (h1peml0). I added a filter to the h1peml0 part so I did not need to add EPICS parts for the SIES signals.
h1susmc2 was rebuilt against stable RCG2.6.2 (it was built last Tues against a modified RCG). The model was restarted at 09:52
The epics gateway between CDS and H1SLOW networks was restarted to support Beckhoff work.
The DAQ was restarted many times. On one restart 9 of the 26 FE went into 0xbad DAQ status. The affected front ends appear to be random and not related to the mx-stream end point distribution.
EDCU channel list had the EX DUST channels removed while those channels are unavailable.