While investigating lost frames, Tx/Rx errors and a non zero CRC for the Corner MSR L8_9 Vertex (EK1521) (the terminal for the fiber connection to the H1 electronics room), the h1ecatc1 computer froze and restarted. I had looked into the chassis housing this terminal in the MSR and had not seen anything obviously wrong with it. However, the error LEDs on the Corner MSR L2 (EL3202-0010) (the temperature probe readout) terminal were both lit. After the computer restarted I restarted the system manager and deleted the configured terminal for the connection to end X (it was disabled because it is not connected), and checked that scanning the modules gave an identical configuration. It did, and I put it in run mode and started PLC1 and PLC2. The previous errors with the EK1521 are gone, but the error LEDs are still red on the EL3202. I have not restarted the EPICS IOCs.