patrick.thomas@LIGO.ORG - posted 18:54, Tuesday 14 May 2013 - last comment - 15:54, Wednesday 15 May 2013(6358)
weather station code changes
Dave B., Patrick T.

This work falls under permit number 3887.

This morning I installed new EPICS IOC code for the weather stations in /ligo/apps/linux-x86_64/epics-3.14.12.2_long_sc. The module code is davis_weather_monitor_ii-1.0.0 and the IOC code is weather_davis_weather_monitor_ii-1.0.0. The targets are in /ligo/lho/h0/target. The IOCs are running in screen on h0epics2.

This was done primarily to change the channel names to reflect the aLIGO PEM standard in T1200221-v5.
I also hard coded the alarm severities for the wind speeds in the database files. The wind speed alarm levels are set by hand and stored in the autoBurt.req files.
The macro substituted database files are now generated from a template and substitutions files when the IOC is compiled.
An iocBoot directory named ioch0_weather_cs was created and the target named h0weatherms was changed to h0weathercs.

Dave renamed the minute trend files to reflect the channel name changes. his alog entry
New medm screens were linked to in the site map that incorporated the channel name changes.
The autoBurt.req files were updated.
Comments related to this report
patrick.thomas@LIGO.ORG - 15:54, Wednesday 15 May 2013 (6388)
The mapping for the channel name changes is attached.