Guardian changes for CHARD Y

I made some guardian changes to turn on the new CHARD Y control filter. I am not sure how well this filter will work for lock acquisition, so I have it set up to engage at POWER_10W.

Comments related to this report
elenna.capote@LIGO.ORG - 20:55, Wednesday 07 December 2022 (66247)

Going to lownoise ASC does not work. The oscillation was a ring up at 0.45 Hz. My guess it that some combination of lower CSOFT Y gain and the reduced CHARD Y bandwidth do not play well. Reverting the CHARD Y bandwidth changes did not avert the lockloss.

This is very odd because I got to this state last night, but I ran through it by hand. I don't understand why it did not work tonight.

At the next lock, I commented out all lownose asc changes to CHARD Y in the guardian, and increased the csoft y gain back to 10. Then, after I ran the lownoise asc guardian state, I made the lower bandwidth changes to chard y: lower gain to 75, turn on FM6 and 9. Everything was fine. Then I tried to lower the csoft y gain to 5. Many ASC loops immediately began to ring up at 0.45 Hz. I quickly returned the CSOFT Y gain to 10.

I am uncommenting the lownoise asc changes for chard y, but keeping the csoft y gain at 10.