Dust Monitor Vacuum Pump Check
FAMIS 23748
Corner Station:
- Sounded okay, slight grating noise
- Pressure at 20.0 inHg, adjusted to 19.0 inHg
- Temperaturs up to 190F on the front of the pump housing
EX:
- Sounded okay
- Pressure at 21.0 inHg, adjusted to 19.0 inHg
- Temperatures up to 175F on the front of the pump housing
EY:
- Sounded okay
- Pressure at 18.0 inHg, adjusted to 19.0 inHg
- Temperatures okay