Displaying report 1-1 of 1.
Reports until 13:26, Friday 28 April 2023
LHO VE
david.barker@LIGO.ORG - posted 13:26, Friday 28 April 2023 - last comment - 16:08, Friday 28 April 2023(69161)
Fri CP1 Fill, not good, trying again at 3pm

Fri Apr 28 13:18:55 2023 INFO: Fill completed in 3min 55secs

Bad Fill.

Even with the new trip temps of -100C today's fill was not good. The TCs started around their nominal limits, in fact TC-B was not used for the fill because it started at -74C and nominal was -70C. TC-A quickly exceeded the -100C trip level.

We will give the TCs time to warm up and try again at 15:00 with new settings: trip=-120C and tc-nom=-90C.

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 15:11, Friday 28 April 2023 (69163)

Second try was successful.

Fri Apr 28 15:02:04 2023 INFO: Fill completed in 2min 4secs

Gerardo confirmed a good fill via camera. New settings are shown in attachment.

 

Images attached to this comment
david.barker@LIGO.ORG - 16:08, Friday 28 April 2023 (69168)

Here is the corrected plot showing the new -120C trip temperature.

Images attached to this comment