WP11163 Remove IFO_UNDISTURBED Guardian node
TJ, Jonathan, Dave:
TJ removed the IFO_UNDISTURBED node from h1guardian1. I removed its channels from H1EPICS_GRD.ini. Jonathan removed H1:GRD-IFO_UNDISTURBED_OK from the DAQ Broadcasters. EDC+DAQ restart were required.
WP11165 h1sqz model change
Daniel, Dave:
Daniel's latest h1sqz model was installed. There were all possible types of DAQ Changes (except datatype change)
fast channels removed | 3 |
fast channels rate increased | 3 |
fast channels rate decreased | 4 |
slow channels removed | 14 |
fast channels added | 5 |
slow channels added | 11 |
WP11153 Add h1cdssdf slow controls SDF
Jonathan, Erik, Dave:
A new h1cdssdf was added to h1ecatmon0 using the next available dcuid (1039) and specific_cpu (16).
Its monitor.req initially monitors the lock-lock-alert settings.
WP11168 New h1oaf model
Jenne, Dave:
Jenne's new h1oaf model was installed. DAQ changes:
fast channels removed | 0 |
slow channels removed | 11 |
fast channels added | 7 |
slow channels added | 11 |
WP11166 New h1calcs model
Jeff, Dave:
Jeff's new h1calcs model was installed. DAQ changes:
fast channels removed | 0 |
slow channels removed | 28 |
fast channels added | 0 |
slow channels added | 136 |
DAQ Restart
Dave, Jonathan:
DAQ and EDC were restarted to support the above changes. No problems except GDS0 needed a second restart to sync its channel list.
DAQ Changes
Full Frame:
Detailed frames lists are available in attached TAR file.
channels removed | 79 |
channels with rate change | 7 |
channels added | 173 |
GDS Broadcaster:
channels removed | 1 (H1:GRD-IFO_UNDISTURBED_OK) |
channels added | 0 |
Changes to the CDS Overview MEDM:
Expanded the CDS section to include the new h1cdssdf difference report. Shrunk the staging-building bakeout in the Vacuum section to make room.
Front End status colours are now ready for O4, previous purple, orange, yellow blocks are now RED.
Tue02May2023
LOC TIME HOSTNAME MODEL/REBOOT
08:51:07 h1lsc0 h1sqz
08:51:42 h1oaf0 h1oaf
08:52:05 h1oaf0 h1calcs
09:19:42 h1lsc0 h1sqz <<< Daniel second change, before DAQ restart
09:22:47 h1daqdc0 [DAQ]
09:22:57 h1daqfw0 [DAQ]
09:22:58 h1daqnds0 [DAQ]
09:22:58 h1daqtw0 [DAQ]
09:23:05 h1daqgds0 [DAQ]
09:23:24 h1susauxb123 h1edc[DAQ]
09:24:00 h1daqgds0 [DAQ] <<<< gds0 second restart
09:25:59 h1daqdc1 [DAQ]
09:26:12 h1daqfw1 [DAQ]
09:26:12 h1daqtw1 [DAQ]
09:26:14 h1daqnds1 [DAQ]
09:26:21 h1daqgds1 [DAQ]
11:58:10 h1seib1 ***REBOOT*** <<< power cycle h1seib1 following IO Chassis power down for DC supply work
11:59:42 h1seib1 h1iopseib1
11:59:55 h1seib1 h1isiitmy
12:00:08 h1seib1 h1hpiitmy