jordan.vanosky@LIGO.ORG - posted 11:20, Tuesday 09 May 2023 (69434)
Functionality Test Performed on EY Turbo Pump

We ran the functionality test on the main turbopump at EY. The scroll pump is started to take pressure down to low 10^-02 Torr, at which time the turbo pump is started, the system reaches low 10^-08 Torr after a few minutes, then the turbo pump system is left ON for about 1 hour, after the hour the system goes through a shut down sequence.
No issues were encountered while performing the functionality test on this station.

EY Turbo:

Bearing Life:100%

Scroll Pump Hours: 198.8

Turbopump hours: 1266

 

Closes WP 11179   FAMIS 24935

 