LVEA Temperature Excursion in Output Arm Area Starting at 2023-May-10 13:46 PDT
J. Kissel, E. Capote, T. Shaffer

We're struggling through alignment of the SRC during lock acquisition, and we looked through some trends of SR3 alignment and we see that it's alignment is quite off in Yaw. TJ said "Oh, well, yeah, the temperature in the VEA has gone bad. That's normal." 

Trusting but verifying, I trended the average of zones in the LVEA, and I disagree -- there as a marked step-change in the LVEA temperature starting at 2023-05-10 13:45 PDT (20:45 UTC), which, over the course of a day has increased the output arm's temperature by 1 deg C, or ~2 deg F.

Perhaps a set point got lost?
Images attached to this report
Comments related to this report
bubba.gateley@LIGO.ORG - 13:33, Thursday 11 May 2023 (69518)
After receiving a call from the control room regarding a temperature increase in the HAM 6 area, Tyler and I looked at the FMCS and found that for some reason, AHU 2 was off, both fans down. There has been some fire panel testing which may have contributed to this issue. AHU 2 was restarted and both fans came back up. Made a few adjustments to the dampers for air flow and all seems to be running as designed. I will continue to monitor. 
jeffrey.kissel@LIGO.ORG - 13:49, Thursday 11 May 2023 (69520)DetChar
AHU = Air Handler Unit

FIXED IT.