Reports until 17:13, Tuesday 30 May 2023
LHO VE (VE)
gerardo.moreno@LIGO.ORG - posted 17:13, Tuesday 30 May 2023 - last comment - 17:26, Tuesday 30 May 2023(70019)
Battery Check at Y2-8 and X2-8

Y2-8
Solar panels are mostly clear and in good condition, all cables are good.
Each battery was checked with a multimeter:
Top battery 13.21 VDC
Bottom battery 12.93 VDC
The LCD readout at the charge controller showed for both batteries 26.10 VDC, measured with clear skies.

X2-8
Solar panels are mostly clear and in good condition, all cables are good.
Each battery was checked with a multimeter:
Right battery 14.66 VDC
Left battery 14.82 VDC
The LCD readout at the charge controller showed for both batteries 29.60 VDC, measured with clear skies.

FAMIS task 22072

Images attached to this report
Comments related to this report
gerardo.moreno@LIGO.ORG - 17:26, Tuesday 30 May 2023 (70021)VE

Ground cable lost its grip, needs more glue.  See photo from X2-8 station.

Images attached to this comment