Displaying report 1-1 of 1.
Reports until 16:13, Saturday 10 June 2023
H1 General (SUS)
anthony.sanchez@LIGO.ORG - posted 16:13, Saturday 10 June 2023 (70329)
Saturday OPS Day Shift End

TITLE: 06/10 Day Shift: 15:00-23:00 UTC (08:00-16:00 PST), all times posted in UTC
STATE of H1: Observing at 137Mpc
CURRENT ENVIRONMENT:
    SEI_ENV state: CALM
    Wind: 7mph Gusts, 5mph 5min avg
    Primary useism: 0.02 μm/s
    Secondary useism: 0.09 μm/s
QUICK SUMMARY:

17:21 UTC a tour group came through the control room.
Confirmed a slow Climb in IMY Mode5. Gain H1:SUS-ITMY_L2_DAMP_MODE5_GAIN was set at -0.04 and I changed it to 0.
Looking at alog 70057 https://alog.ligo-wa.caltech.edu/aLOG/index.php?callRep=70057  I will try a gain of +0.01

Lockloss 19:50 UTC of unknown cause.   

Locking Summary:
No Initial alignment was done before trying to lock again.
DRMI 1f didn't lock but i let it go to Aquire PRMI which then locked and we went on up.
NOMINAL_LOW_NOISE Reached at 21:04 UTC
Intention bit set to Observing 21:09 UTC.

Violin Modes:
ITMY mode 8 is increasing again. I will take the gain to 0 then then up to +0.04 as described in the following alog.  
https://alog.ligo-wa.caltech.edu/aLOG/index.php?callRep=70057
That singular change of gain did not make any difference, but taking the gain back to 0 then turning on FM7 which is a -30 deg phase change then bringing the gain back up to 0.04 did start bringing ITMY Mode 5 down. Tagging SUS

IFO Current Status: NOMINAL_LOW_NOISE & Observing

 

Displaying report 1-1 of 1.