Puppet updates as part of WP 11245
As one of the last steps of WP 11245 we formally add the new raw trend archive directory to the nds server's puppet config.  Today I ran puppet in a verbose and noop mode on all the daqd systems to see what differences there were (we expected a difference in nds0).  I then reviewed the differences and updated the puppet config to match what is in production.  This was a good run to do we found a few things that we had changed in production that we had not put in puppet.

 * nds0 - added the new archive raw trend directory.
 * nds1 - found that we had not added the last archive raw trend directory to puppet, so added that.
 * tw0/1 - put into puppet a smaller circular buffer size that we had added to the systems to deal with larger channel lists.
 * gds1 - updated the firewall settings to match gds0, we had done some experimentation in the past to trouble shoot items.

Now puppet matches reality and is a faithful record of the daqd configs.

In addition I removed the mount to /opt/cdscfg from both the daqd systems and the daqd puppet.  This is brought in due to front end needs on the puppet, but is not required for daqd and just causes issues when we switch boot servers.