PSL Chiller Flow Rate Lowered (WP 11209)

J. Oberling, R. Short

Robert requested that we lower the PSL chiller flow rate in an attempt to lower the vibration on the PSL table.  Ryan and I did this at ~17:02 UTC (10:02 PDT); we lowered the flow by slightly adjusting the chiller's internal bypass, it changed from ~3.2 lpm to ~2.6 lpm (roughly half-way between our old operating flow and our observed minimum).  The laser was fine with this change; we did see an expected slow increase in the water temperature and in the Amp/DB temperature.  We are monitoring the PSL as it thermalizes with this new cooling flow rate and will update if anything adverse occurs (we will keep a close eye on air bubbles).  I am leaving WP 11209 open for now as we may need to adjust the flow rate again, depending on what Robert finds with this first change.