We ran the functionality test on the main turbopumps in the corner during Tuesday Maintenance (8/1/23). The scroll pump is started to take pressure down to low 10^-02 Torr, at which time the turbo pump is started, the system reaches low 10^-08 Torr after a few minutes, then the turbo pump system is left ON for about 1 hour, after the hour the system goes through a shut down sequence.
No issues were encountered while performing the functionality test on this 3 stations.
Output Tube Turbo: Note: The flex hose connecting the turbo exhaust to the WTCB1 header line has been physically disconnected.
Bearing Life:100%
Turbo Hours: 5617
Scroll Pump Hours: 5558 - Needs Tip Seal Swap
XBM Turbo: Note: The flex hose connecting the turbo exhaust to the WTCB1 header line has been physically disconnected.
Bearing Life:100%
Turbo Hours: 782
Scroll Pump Hours: 780.5
YBM Turbo:
Bearing Life:100%
Turbo Hours: 599
Scroll Pump Hours: 1875
Closes WP 11340
This work closes the following FAMIS tasks:
23521
23593
23641