Reports until 10:59, Tuesday 29 August 2023
H1 PEM
oli.patane@LIGO.ORG - posted 10:59, Tuesday 29 August 2023 (72515)
Quarterly Dust Monitor Testing (FAMIS 23738)

FAMIS#23738 (not closing due to PSL check not having been done yet)

Previous check: 68779

**PSL Anteroom and Laser Room will be done at a later date when going in there is required for other tasks.

Location Dustmon Zero Count Test Flow Rate (LPM)
Corner Station
LVEA HAM2 LVEA 5 Not in use
  HAM6 LVEA 6 Pass 2.8
  BSC1 LVEA 10 Pass 2.78
PSL Laser Room PSL 101 **  
  Anteroom PSL 102 **  
Labs Optics Lab LAB 1 Pass 2.8
  Vacuum Prep Lab LAB 2 Pass adjusted to 2.7
  PCAL Lab LAB 3 Not in use
Diode Room Diode Room DR 1 Pass 2.73
CER Handheld 1 HH1 Not there  
  Handheld 2 HH2 Not there  
  Handheld 3 HH3 Not there  
  Handheld 4 HH4 Not there  
  Handheld 5 HH5 Not there  
Outbuildings
End Stations EX VEA EX VEA 1 Pass 2.8
  EY VEA EY VEA 2 Pass on 2nd try 2.7
FCES HAM8 HAM8 Pass adjusted 2.3 -> 2.7