I have written a python script which generates an MEDM showing the four BSC temperature sensors and the settings used to convert voltage to DegF (and DegC).
Please reference DCC-T0900287 for details.
Fil measured BSC1's skin temperature to be 69.0 - 69.5 F using the hand held remote temp sensor.
BSC1 initially came back with a low and noisy voltage. Richard reattached the cabling which fixed the issue.
To open this MEDM, from a recent SITEMAP, it is the last entry in the FMCS pull down (the PEM pull down is totally full)
The gain and offset are set with EPICS input records. They can be changed via channel access, and are being configuration controlled by SDF.