david.barker@LIGO.ORG - posted 12:07, Friday 15 September 2023 (72899)
Added GPS channels to Picket Fence MEDM

During this week's Tuesday maintenance, we added two GPS channels to the Picket Fence system:

H1:SEI-USGS_SERVER_START_GPS : Start time of server on nuc5
H1:SEI-USGS_SERVER_GPS: server's current processing time, updates every few seconds when running

I have added these channels to the Picket Fence MEDM, along with a "Server Running" status rectangle which turns RED if the SERVER_GPS time lags current GPS by a minute or more.

I also added Picket Fence to the CDS section of the CDS Overview. The circular RED/GREEN LED uses the same display logic as above, and the PKT button opens the Picket Fence MEDM.

The attachment below shows the new H1CDS_PICKET_FENCE MEDM (computer generated) and a snipet of the CDS Overview showing the CDS section.
 