Reports until 12:03, Friday 22 September 2023
LHO VE
david.barker@LIGO.ORG - posted 12:03, Friday 22 September 2023 - last comment - 12:10, Friday 22 September 2023(73056)
Fri CP1 Fill

Fri Sep 22 10:09:28 2023 INFO: Fill completed in 9min 24secs

Travis confirmed a good fill curbside.

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 12:10, Friday 22 September 2023 (73057)

Note that the TCs only dropped to -150C and -144C for A, B respectively because the outside air temp was only 49F at 10am (due to fog?). We might have to increase the trip temp from -130C to -120C soon.