Reports until 15:05, Saturday 28 October 2023
LHO FMCS (Lockloss)
camilla.compton@LIGO.ORG - posted 15:05, Saturday 28 October 2023 - last comment - 15:21, Saturday 28 October 2023(73800)
Lockloss at 21:58UTC

Lockloss after being in NLN for 5 minutes. 1382565549.  Hadn't yet got into Observing after 20:46UTC lockloss 73799

Third lockloss of the shift. No obvious reason again, environment, LSC and ASC signals look fine. 

LVEA temperatures have a 0.5deg excursion but looks to be turning around, plot attached. The outside temperatures have changed a lot this week and we were seeing smaller excursions on Thursday/Friday.  Tagging FMCS.

Images attached to this report
Comments related to this report
camilla.compton@LIGO.ORG - 15:21, Saturday 28 October 2023 (73804)

Can see that LVEA temperature sensor 5A changed 1.7degF and some of the close optics show alignment drifts with this: PR2, MC2, ITMY. Plot attached. This could be the cause of the last two locklosses today.

Images attached to this comment