Displaying report 1-1 of 1.
Reports until 12:28, Thursday 16 November 2023
LHO General
eric.otterman@LIGO.ORG - posted 12:28, Thursday 16 November 2023 (74237)
Low temp in Mid Y this morning.
The low temperature in Mid Y this morning was the result of a malfunctioning heater. Both SCRs had burned up so there was no heating control available. I bypassed both SCRs and wired straight from the line voltage fuses. The heat staging required rewiring as it had been wired to bring on all stages of heating with only a single stage heating command. 