Mon Nov 27 10:04:41 2023 INFO: Fill completed in 4min 38secs
Jordan confirmed a good fill curbside.
The fill only barely completed, TC-A flat lined at -90.0C and for just one sample went to -90.1C which triggered the end-of-fill. I've increased the trip temp to -80C. The site is experiencing freezing fog, temp=-3C. I suspect TC icing may be an issue.