Displaying report 1-1 of 1.
Reports until 13:08, Tuesday 28 November 2023
LHO VE
jordan.vanosky@LIGO.ORG - posted 13:08, Tuesday 28 November 2023 - last comment - 11:28, Tuesday 05 December 2023(74453)
Functionality Test Performed on EY/MY Turbo Pumps

Jordan

We ran the functionality test on the main turbopumps in MY and EY during Tuesday Maintenance (11/28/23). The scroll pump is started to take pressure down to low 10^-02 Torr, at which time the turbo pump is started, the system reaches low 10^-08 Torr after a few minutes, then the turbo pump system is left ON for about 1 hour, after the hour the system goes through a shut down sequence.
 

MY Turbo:

Bearing Life:100%

Turbo Hours: 208

Scroll Pump Hours: 74

EY Turbo:

Scroll pump made a grinding sound after getting to ~ 5E-2 Torr. I closed all valves and stopped the test. The scroll pump only has 200 hours on it so it will be disassembled to figure out the source of the noise. I have swapped the scroll pump with a new ISP250, but did not have time to run the turbo test. I will resume next tuesday and add a comment to this alog with the EY results.

Closing WP 11544 and FAMIS 24917

Comments related to this report
jordan.vanosky@LIGO.ORG - 11:28, Tuesday 05 December 2023 (74606)

After swapping the scroll pump, I ran the functionality test on the EY main turbopump during Tuesday maintenance, no issues were encountered during this test.

Turbo Hours: 1275

Scroll Pump Hours: 72

Bearing life: 100%

Closing WP 11553 and FAMIS 24941

Displaying report 1-1 of 1.