david.barker@LIGO.ORG - posted 10:25, Friday 01 December 2023 (74518)
Fri CP1 Fill, manually canceled after fill completed

Fri Dec 01 10:11:37 2023 ALERT: Fill done (errors) in 11min 33se

Gerardo confirmed a good fill curbside, and then had to manually cancel the fill because the TCs did not fall below the trip temps.

Trip = -80C, TC-A_min = -77.1C, TC-B_min = -72.0C

I have increased the trip temp to -75C. I suspect this will be very temporary since outside temps are forcast to be above freezing in a day for so.

Images attached to this report