Reports until 08:13, Tuesday 05 December 2023
LHO General
eric.otterman@LIGO.ORG - posted 08:13, Tuesday 05 December 2023 (74593)
Chilled water loop temperatures at EX, EY
The chillers were resetting their set points based on outdoor air temperature, so the last week of cold weather followed by several days of warmer weather was causing issues for the PID loops in the programming. I disabled the outdoor air temperature reset feature on the chillers to keep them from deviating from their initial set points. 