One of the two CER AC banks turned off temporarily

One of the ACs in the CER is again running at the 13.1 Hz frequency of the MC baffle near HAM3, producing broad harmonics in DARM. I shut it down at 0:34 UTC and will turn it on in a couple of hours to see if this moves the peak away from 13.1 Hz.