Displaying report 1-1 of 1.
Reports until 10:46, Sunday 31 December 2023
H1 CDS
david.barker@LIGO.ORG - posted 10:46, Sunday 31 December 2023 (75095)
Site slight power glitch 06:53:55 PST

Ryan, Richard, Dave:

The GC UPS reported time on battery this morning between 06:53:56 - 06:54:01 PST.

Attached fast mains mon channels show a slight dip in voltage for all three phases as seen in the corner station, lasting for only about 5 cycles. H1 and CDS rode through this with no issues, H1 stayed locked.

Ryan walked the MSR and GC server rooms, nothing untoward was found.

 

 

Images attached to this report
Displaying report 1-1 of 1.