Reports until 08:50, Wednesday 17 January 2024
H1 CDS
david.barker@LIGO.ORG - posted 08:50, Wednesday 17 January 2024 - last comment - 08:53, Wednesday 17 January 2024(75435)
FMCS IOC running as systemd service, auto-restart code running

Patrick, Jonathan, Erik Dave:

While the fmcs ioc continues to be unstable, I wrote an auto-restart script which restarts the IOC if its EPICS values flatline for more than 9 minutes.

In order to control the IOC code we moved it from a screen environment to a procServ, and converted the code to a systemd service.

The auto-restart code runs as david.barker on cdsmanager. Every minute it gets the value of the EX chiller yard water temperature channel H0:FMC-EX_CY_H2O_SUP_DEGF.

If the value of this channel does not change for 9 successive minutes, the code restarts the fmcs_ioc.service on fmcs-epics-cds

    ssh root@fmcs-epics-cds 'systemctl restart fmcs_ioc.service'

I started the auto-restart code at 23:12 PST Tue night, since that time there have been 3 auto-restarts

    Tue 16 Jan 2024 11:35:41 PM PST
    Wed 17 Jan 2024 02:29:52 AM PST
    Wed 17 Jan 2024 04:32:58 AM PST
 

Full details can be found in the wiki page h0fmcsbacnet

Comments related to this report
david.barker@LIGO.ORG - 08:53, Wednesday 17 January 2024 (75437)

Attachment shows the three overnight auto-restarts, each preceded by 9 minute flatlines

Images attached to this comment