LVEA temperatures have ticked up a couple of degrees, namely in zone 4 which makes up all of the east bay extending to BSC2. This is to be expected given all the additional heat-load via cleanrooms (mega and otherwise). As of the writing of this log, average space temperature for Zone 4 is 70.56F. Roughly 3 degrees above setpoint with the peak temp of 73.5F at HAM7. The previous setpoint for Zone 4 was 67.5F. I have just changed this to 65.5F remotely and will monitor throughout the weekend. This change is likely to trigger a high-level alarm. That alarm should be disregarded. T. Guidry