LHO FMCS
eric.otterman@LIGO.ORG - posted 10:44, Friday 02 February 2024 (75707)
LVEA temperatures
The air handler currently running had its bypass dampers open, so the airflow was bypassing the cooling coil and relying on outside air for space cooling. Because its dampers are manually set, it was not able to reach supply air setpoint. I manually closed the bypass damper which allowed airflow through the cooling coil again and the unit is now reaching supply air setpoint. This is the reason for the sudden drop in space temps in the trend.