david.barker@LIGO.ORG - posted 13:37, Wednesday 07 February 2024 - last comment - 13:45, Wednesday 07 February 2024(75763)
Long range dolphin IPC errors caused by IPMI reset of chassis-intrusion-sensor

I have been upgrading my hourly cds_report.py code to access the IPMI system and report on sensor warnings and power supply failures. One of the systems I am scanning, h1cdsrfm, has its chassis intrusion sensor triggered (the lid was removed at some point in the past). To clear this warning, at 13:09 I cleared the sensor using the IPMI web interface. This appears to have caused a glitch in the long-range-dolphin IPC channels. We saw IPC errors over EX, EY and CS models (see attachement).

I have DIAG_RESET these transient errors.

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 13:45, Wednesday 07 February 2024 (75764)

This had happened before on 21 Sep 2018 and is covered by FRS11512

I have updated the ticket with today's glitch, no need to open a new ticket.