Cabling between BSC3 and BSC7 now supported by a cable tray. See attached picture. Cabling previously held in place by zip ties and velcro. Concern if zip ties failed, vacuum piping on GV2 could be damaged. Good catch by the vacuum team.
During installation of cable tray, found that both SUS-R5 and SUS-R6 racks were not grounded. After discussing with Robert/Richard, we decided to ground the racks. Robert will compare before/after once we reach NLN.
If grounding of racks needs to be reverted, the 6 awg grounding cables can be disconnected at each rack.