(David Barker, Cyrus Reed, James Batch) LHO experienced a 2 second power fail at 00:40:43 PDT and a power glitch at 06:06 PDT which caused front end reboots. Also affected were both CDS file servers. The main file server entered a read-only state, while the backup file server locked up and was unresponsive. Both file servers were restored by 08:30 PDT. All front-end computers were powered off, as several were not logically attached to their I/O chassis. On power up, the following computers still could not find the I/O chassis: h1seib1 h1seih45 h1sush2b h1susquadtst h1susex h1susexaux In each case, turning the power switch on the front of the I/O chassis from on to off to on caused the I/O chassis to power up. The computers were then power cycled to get the I/O chassis reattached. At this point, there were IPC problems in which channels could not be received from the following computers: h1lsc0 h1asc0 h1seih23 h1seih16 h1seib2 In order to correct this problem, the Dolphin switches in the MSR needed to be power cycled, which in turn required all computers in the MSR that were attached to the Dolphin network to be power cycled. Once this was accomplished, and a few models manually restarted, all appears to be well. The system is back in operation as of 11:30 PDT.