david.barker@LIGO.ORG - posted 12:01, Wednesday 17 July 2024 (79194)
Atomic Clock has gone out of sync with GPS again

Following the resync of the atomic clock on Monday, it went out of sync again today starting at 09:53 PDT. This time it is -0.106 Seconds out from GPS.

Previous out-of-syncs this year: 04 May = -0.298 S, 15 July = 0.242 S

To "green up" the corner timing status, I have temporarily increased the comparitor's tolerance from 1uS to 0.999 Seconds.

 