Reports until 15:58, Thursday 01 August 2024
H1 SEI
jim.warner@LIGO.ORG - posted 15:58, Thursday 01 August 2024 - last comment - 09:16, Friday 02 August 2024(79421)
HAM2-3 Isolation loop gains adjusted, too aggressive before, much less gain peaking around 40hz

After my discovery in this alog that the phase and gain margins were pretty tight on HAM2, I did a bunch of olg measurements on HAM2&3 and tweaked the loop gains and boost filters to reduce the gain peaking around 40 hz. More or less all DOFs on these chambers had ugfs around 35hz and phase margins around 5 degrees. Kinda suprised this was stable, I haven't looked at these in a long time. I do wonder if something is funky with the measurement, but I don't know what that would be. Attached image shows one of the worst, the Z dof on HAM3. Blue and yellow are the new loops gain and sensitivity, red and purple are the old loop. The filter changes might make things slightly worse in the 10-20 hz region, but that should be somewhat compensated by the HEPI to ISI feedforward. Should improve the  30-40 hz motion somewhat though.

Images attached to this report
Comments related to this report
jim.warner@LIGO.ORG - 09:16, Friday 02 August 2024 (79430)

Legend is reversed on the plot. What was old is new, etc.